Products Description
ProSoft MVI56-MNETR Modbus TCP/IP Interface Module with Reduced Data Block

Technical Specifications
Model:MVI56-MNETR
Brand:ProSoft
Product type:ControlLogix Single Slot Modbus TCP/IP Communication Module
Backplane power:800mA @5VDC,3mA@24VDC
Ethernet port:1*10/100Mbps RJ45,auto MDIX
Modbus TCP:Client & Server mode
User register database:max 5000 pcs 16-bit registers
Display:4 character scrolling alpha-numeric LED
Weight:0.42kg
Operating temperature:0℃ ~ +60℃
Storage temperature:-40℃ ~ +85℃
Relative humidity:5%~95%,non-condensing
Dimension:1756 single slot standard size
Certification:CE,UL,Class I Division2
System compatibility
MVI56-MNETR belongs to ProSoft MVI56 series ControlLogix chassis communication module.
Install directly into 1756 ControlLogix rack single slot.
Compatible with ControlLogix L6x,L7x series controllers,Studio5000 environment.
Connect Modbus TCP instruments,flow meter,pressure transmitter,Modbus PLC and SCADA host.
Suitable for water treatment,petrochemical,power plant,remote rack control system renovation and spare replacement.
Function
Realize bidirectional data exchange between ControlLogix PAC and Modbus TCP network devices.
Reduced data block design,decrease backplane data load,suitable for remote chassis application.
Support Modbus TCP client and server dual working mode.
Built-in web server for module status view,diagnostic and firmware upgrade.
ProSoft Configuration Builder(PCB) for parameter configuration.
Provided AOI add-on instruction and sample ladder logic for easy integration into Logix project.
Support CF card for configuration backup and fast on-site module replacement.
Communication statistical counters and fault diagnostic function.
Installation
Insert module into 1756 ControlLogix chassis single slot and lock.
Power supplied from ControlLogix backplane.
Connect Modbus TCP network cable to RJ45 ethernet port.
Set IP address,Modbus client/server command list and register mapping in PCB software.
Import AOI instruction into Studio5000 project,download program and module configuration.
Check LED indicators after power-on.
Interface
1*10/100Mbps RJ45 ethernet port,1756 backplane connector,CF card slot,LED indicators:OK,APP,ERR,ETH.
Feature
Standard single-slot ControlLogix form factor,plug and play in 1756 rack.
Reduced backplane data block,reduce controller backplane bandwidth occupation.
Support Modbus TCP client and server,connect multiple Modbus TCP field devices.
4 character scrolling LED,display IP,status and fault information directly.
Web diagnostic page for remote troubleshooting.
CF card configuration cloning,quick replacement without reconfiguration.
Shock and vibration resistant design,stable long-term operation in industrial cabinet.
Diagnostic
Check OK and ETH LED;communication failure:verify ethernet wiring,IP subnet and firewall;data abnormal:check Modbus command list,register mapping and backplane AOI logic.
Product Brief
MVI56-MNETR is ProSoft MVI56 series in-chassis Modbus TCP communication module for ControlLogix.
With reduced data block design,it connects Rockwell ControlLogix controllers with Modbus TCP field instruments and PLCs,widely used in process automation remote rack control projects.

Disclaimer
Product parameters are for reference only and shall not be used as pricing basis. Goods are in short supply and will be powered on for inspection before shipment. Overseas delivery lead time is 3-7 working days. The product is only used for equipment maintenance and transformation.