Products Description
Fisher GG04418X012 Magnetic Array Mounting Kit

Technical Specifications
Model:GG04418X012 Brand:Fisher Product Type: DVC6200 magnetic array arc mounting bracket kit
Module Feature
Fisher GG04418X012 is dedicated curved mounting bracket assembly for DVC6200 linkage-less digital valve controller magnetic feedback array. Precision machined metal plate with multi-position mounting holes, used to fix the magnetic strip onto valve stem. It ensures correct alignment between magnetic array and non-contact sensor of DVC6200. This part is discontinued. Widely used for retrofit and maintenance of Fisher globe control valves equipped with DVC6200.
Working principle: Secure magnetic array and maintain fixed gap for non-contact travel sensing Onboard components: Curved metal mounting plate, fastening bolts, locating washers
LED indicators
Not equipped
Hardware self-diagnosis
Visual inspection, bracket deformation & crack inspection, magnetic array alignment test, valve stroke feedback verification after installation
Programming software
No dedicated software required
Mechanical & Structure
Mounting: Installed on valve stem / actuator pushrod Protection class:IP66
Environmental
Operating temperature:-40℃ ~ +120℃ Ambient humidity:5~95% non-condensing Certification:CE Status:Fisher DVC6200 positioner mounting spare kit
System compatibility
Compatible with Fisher DVC6200 digital valve controller, match with 657/658/667 series pneumatic diaphragm actuators and globe control valves.
Function
GG04418X012 is magnetic array mounting bracket kit manufactured by Fisher. It firmly mounts the magnetic feedback strip on valve stem, keeps the proper distance and parallelism between magnetic array and positioner sensor. Correct installation guarantees accurate non-contact stroke feedback. Bent or misaligned bracket will cause travel reading error and poor positioning performance. It is essential spare part for DVC6200 installation and overhaul.
Installation
Follow lockout/tagout safety procedure before installation. Isolate pipeline and release process pressure. Fix GG04418X012 bracket on valve stem, install magnetic array and adjust gap. Fasten bolts crosswise. Reassemble valve, mount DVC6200 and run auto-calibration, verify stroke feedback signal.
Interface
Bolt mounting on valve stem, magnetic array fixed on bracket surface, no LED indicators on GG04418X012.
Diagnostic
Incorrect travel feedback: Bracket deformation or magnetic array misalignment. Unstable position signal: Loose mounting bolts. Calibration failure: Wrong gap between magnet and sensor.

Product Brief
GG04418X012 Fisher DVC6200 curved magnetic array mounting bracket kit,for installing non-contact magnetic feedback strip on valve stem,positioner installation spare part.