Products Description
Fireye ZB230UVSC BurnerLogix Burner Management Chassis

Technical Specifications
Model:ZB230UVSC Brand:Fireye Product Type: BurnerLogix Z series microprocessor burner control chassis with built-in UV self-check flame amplifier
Control Feature:
Amplifier type: UV self-check flame amplifier
Sequence control: Pre-purge, ignition, flame supervision, post-purge and safety lockout
Compatible flame detector: Fireye UV self-check series flame scanners
Support on/off, high-low-off and modulating burner operation modes
Built-in fault logging and lockout history storage
Electrical Parameters:
Supply voltage: 230 VAC, 50/60Hz
Flame input terminal: Dedicated UV scanner wiring terminals
Relay outputs: Fuel valve, ignition, alarm and auxiliary relay outputs
Digital inputs: Safety interlock, pressure switch, temperature switch inputs
Communication: Optional communication module for remote monitoring
Mechanical & Structure:
Housing: Standard metal chassis for cabinet DIN rail mounting
Front panel: LED status indicators, reset button
Compatible display: BLV512 OLED or BLL510 LCD display (sold separately)
Plug-in programmer module slot
Environmental:
Operating temperature: -20℃ ~ +60℃
Ambient humidity: 0~90% non-condensing
Certification: UL, FM approved
Weight: Approx 1.8kg
System compatibility
ZB230UVSC belongs to Fireye BurnerLogix Z series burner management family. Compatible with Fireye UV self-check flame scanners such as UV90L-1. Matches BLV512 / BLL510 display units, plug-in programmer modules and flame scanner accessories. Widely used for gas, oil boiler and furnace burner combustion safety control and spare replacement.
Function
ZB230UVSC is BurnerLogix integrated burner control chassis manufactured by Fireye. It integrates burner sequencing logic and UV self-check flame amplifier in one chassis. The UV self-check amplifier continuously validates the health status of UV flame scanner during burner operation. It executes full burner cycle including pre-purge, ignition trial, flame monitoring and post purge. When flame loss or scanner fault is detected, the controller triggers safety lockout and cuts fuel supply to prevent explosion risk. It stores fault history for quick maintenance diagnosis. Widely deployed on industrial boilers and furnaces for burner safety control spare replacement.
Installation
Follow lockout/tagout safety procedure before installation. Mount ZB230UVSC chassis inside control cabinet on DIN rail. Install programmer module and optional display module. Wire AC power, safety interlock switches, ignition and fuel valve relays. Connect UV self-check flame scanner wiring strictly following Fireye wiring diagram. Complete burner cold test and firing commissioning, verify flame signal and safety lockout function.
InterfaceAC power terminal block,flame scanner input terminals,digital interlock inputs,relay output terminals,programmer module slot,LED indicators & reset button for Fireye ZB230UVSC.
FeatureOriginal Fireye ZB230UVSC BurnerLogix chassis,230VAC power,built-in UV self-check flame amplifier,supports self-check UV scanners,full burner sequence control,UL & FM safety certified. This spare unit is used for industrial boiler burner sequence and flame safety system maintenance and hardware replacement.
DiagnosticFlame lockout: Inspect UV scanner lens, optical alignment, scanner wiring and flame signal level. Scanner self-check fault: Verify UV scanner model match, supply wiring and scanner aging status. Interlock lockout: Check external pressure/temperature limit switches and interlock loop continuity. No power: Check 230VAC supply voltage and internal fuse integrity. Cannot reset lockout: Review fault history log and clear root cause before manual reset.
Product BriefZB230UVSC is Fireye BurnerLogix Z series 230VAC burner management chassis with integrated UV self-check amplifier, used for gas/oil boiler burner sequencing and flame safety interlock,classic spare for industrial furnace combustion control.

DisclaimerAll parameters are for reference only and shall not be used as the basis for quotation. Goods are scarce, overseas delivery lead time is 3-7 working days. It is only used for equipment maintenance and replacement.